Spenningsfall-kalkulator

Estimer spenningsfallet over en kabelstrekning med NEC-formelen, basert på tverrsnitt og lengde.

Introduksjon

Voltage Drop Calculator - Estimate voltage drop over a wire run using the NEC formula, by gauge and length. Enter Source voltage (V), Current (A), One-way length (ft), Wire gauge, Conductor material, Phase to get an instant result.

Formel

NEC Chapter 9, Table 8 approximate method: VD = (2 × K × I × L) / CM for single-phase, or VD = (√3 × K × I × L) / CM for three-phase, where K = 12.9 ohm-cmil/ft for copper (21.2 for aluminum), I is load current, L is one-way conductor length in feet, and CM is the conductor's circular-mil area.

Steg for steg

  1. Enter the Source voltage (V).
  2. Enter the Current (A).
  3. Enter the One-way length (ft).
  4. Enter the Wire gauge.
  5. Enter the Conductor material.
  6. Enter the Phase.
  7. Click Calculate to see your result instantly.

Eksempel fra virkeligheten

Example: With Source voltage (V) = 120, Current (A) = 20, One-way length (ft) = 100, Wire gauge = 12, Conductor material = copper, Phase = no, the Voltage Drop Calculator gives Voltage Drop V: 7.902, Voltage Drop Pct: 6.585, Circular Mils Used: 6530.

Ofte Stilte Spørsmål

What voltage drop percentage is acceptable?
The NEC does not mandate a limit for most branch circuits, but its informational notes recommend keeping voltage drop to 3% or less on a branch circuit and 5% or less total (feeder + branch circuit combined) for reasonable efficiency and equipment performance.
Why does one-way length matter, not round-trip?
The formula already accounts for both the outgoing and return conductor (via the factor of 2 for single-phase, or √3 for three-phase), so you enter only the one-way distance from source to load.
Does wire material matter?
Yes - aluminum has higher resistance than copper for the same gauge, so its K constant (21.2) is larger, producing more voltage drop than copper (K=12.9) at the same size and length.
What inputs does the Voltage Drop Calculator need?
You'll need to provide: Source voltage (V), Current (A), One-way length (ft), Wire gauge, Conductor material, Phase. All fields use sensible defaults, so you can see a working example immediately and then adjust the values to match your own numbers.
How accurate is the Voltage Drop Calculator?
The Voltage Drop Calculator gives an estimate. Formula used: NEC Chapter 9, Table 8 approximate method: VD = (2 × K × I × L) / CM for single-phase, or VD = (√3 × K × I × L) / CM for three-phase, where K = 12.9 ohm-cmil/ft for copper (21.2 for aluminum), I is load current, L is one-way conductor length in feet, and CM is the conductor's circular-mil area. Actual outcomes vary with factors the formula does not capture, so treat the result as a guide, not a guarantee. Entering realistic, correct values gives the most useful result.
Is the Voltage Drop Calculator free to use?
Yes, the Voltage Drop Calculator is completely free, requires no signup, and runs instantly in your browser.

Om Spenningsfall-kalkulator

Voltage drop occurs when current flows through a wire with resistance, causing the voltage at the load end to be lower than at the source. Excessive voltage drop causes equipment to underperform, motors to overheat, and lighting to dim noticeably. The Voltage Drop Calculator helps you determine the voltage drop for any wire run and whether it meets the National Electrical Code recommended limits. The NEC recommends limiting voltage drop to 3 percent for branch circuits and 5 percent total for branch circuit plus feeders combined. For a 120-volt circuit, 3 percent is 3.6 volts, meaning the load should see at least 116.4 volts. For a 240-volt circuit, 3 percent is 7.2 volts. Voltage drop is calculated using Ohm's Law: voltage drop equals current times resistance of the conductor. The resistance of a wire depends on the material (copper or aluminum), the wire gauge (AWG), and the length of the run. For a round trip (both hot and neutral conductors), the effective length is doubled. Copper wire resistance per 1,000 feet by gauge: 14 AWG has approximately 3.07 ohms per 1,000 feet. 12 AWG has approximately 1.93 ohms. 10 AWG has approximately 1.21 ohms. 8 AWG has approximately 0.764 ohms. For a specific run length, the resistance is proportional to the length. For a 100-foot run (200-foot total round trip) of 12 AWG copper carrying 15 amps: resistance equals (200/1000) times 1.93, which equals 0.386 ohms. Voltage drop equals 15 times 0.386, which equals 5.79 volts. On a 120-volt circuit, this is 4.8 percent, exceeding the 3 percent recommendation. Upsizing to 10 AWG would reduce the voltage drop to approximately 3 percent. This calculator helps you determine the appropriate wire gauge for long runs, evaluate existing wiring for compliance, and plan circuits for outbuildings, detached garages, or landscape lighting where long wire runs are common.