Voltage Drop Calculator
Calculate voltage drop across a wire run to ensure circuits meet NEC recommended limits.
Amortization schedule
| # | Payment | Principal | Interest | Balance |
|---|---|---|---|---|
Growth over time
| Year | Invested | Value |
|---|---|---|
Introduction
Voltage Drop Calculator - Estimate voltage drop over a wire run using the NEC formula, by gauge and length. Enter Source voltage (V), Current (A), One-way length (ft), Wire gauge, Conductor material, Phase to get an instant result.
Formula
NEC Chapter 9, Table 8 approximate method: VD = (2 × K × I × L) / CM for single-phase, or VD = (√3 × K × I × L) / CM for three-phase, where K = 12.9 ohm-cmil/ft for copper (21.2 for aluminum), I is load current, L is one-way conductor length in feet, and CM is the conductor's circular-mil area.
Step-by-step
- Enter the Source voltage (V).
- Enter the Current (A).
- Enter the One-way length (ft).
- Enter the Wire gauge.
- Enter the Conductor material.
- Enter the Phase.
- Click Calculate to see your result instantly.
Real-world example
Example: With Source voltage (V) = 120, Current (A) = 20, One-way length (ft) = 100, Wire gauge = 12, Conductor material = copper, Phase = no, the Voltage Drop Calculator gives Voltage Drop V: 7.902, Voltage Drop Pct: 6.585, Circular Mils Used: 6530.
Frequently Asked Questions
What voltage drop percentage is acceptable?
Why does one-way length matter, not round-trip?
Does wire material matter?
What inputs does the Voltage Drop Calculator need?
How accurate is the Voltage Drop Calculator?
Is the Voltage Drop Calculator free to use?
About the Voltage Drop Calculator
Voltage drop occurs when current flows through a wire with resistance, causing the voltage at the load end to be lower than at the source. Excessive voltage drop causes equipment to underperform, motors to overheat, and lighting to dim noticeably. The Voltage Drop Calculator helps you determine the voltage drop for any wire run and whether it meets the National Electrical Code recommended limits. The NEC recommends limiting voltage drop to 3 percent for branch circuits and 5 percent total for branch circuit plus feeders combined. For a 120-volt circuit, 3 percent is 3.6 volts, meaning the load should see at least 116.4 volts. For a 240-volt circuit, 3 percent is 7.2 volts. Voltage drop is calculated using Ohm's Law: voltage drop equals current times resistance of the conductor. The resistance of a wire depends on the material (copper or aluminum), the wire gauge (AWG), and the length of the run. For a round trip (both hot and neutral conductors), the effective length is doubled. Copper wire resistance per 1,000 feet by gauge: 14 AWG has approximately 3.07 ohms per 1,000 feet. 12 AWG has approximately 1.93 ohms. 10 AWG has approximately 1.21 ohms. 8 AWG has approximately 0.764 ohms. For a specific run length, the resistance is proportional to the length. For a 100-foot run (200-foot total round trip) of 12 AWG copper carrying 15 amps: resistance equals (200/1000) times 1.93, which equals 0.386 ohms. Voltage drop equals 15 times 0.386, which equals 5.79 volts. On a 120-volt circuit, this is 4.8 percent, exceeding the 3 percent recommendation. Upsizing to 10 AWG would reduce the voltage drop to approximately 3 percent. This calculator helps you determine the appropriate wire gauge for long runs, evaluate existing wiring for compliance, and plan circuits for outbuildings, detached garages, or landscape lighting where long wire runs are common.