Sikringsstørrelse-beregner
Find den korrekte sikringsstørrelse ved hjælp af NEC's 125 %-regel for kontinuerlig belastning.
Afdragsplan
| # | Betaling | Hovedstol | Renter | Restgæld |
|---|---|---|---|---|
Vækst over tid
| År | Investeret | Værdi |
|---|---|---|
Introduktion
Fuse Size Calculator - Find the correct fuse size using the NEC 125% continuous-load rule. Enter Continuous load (A) to get an instant result.
Formel
Same NEC 210.20(A) 125% continuous-load rule used for breakers applies to fuse selection: required rating = continuous load × 1.25, rounded up to the next standard NEC 240.6(A) size.
Trin for trin
- Enter the Continuous load (A).
- Click Calculate to see your result instantly.
Eksempel fra virkeligheden
Example: With Continuous load (A) = 16, the Fuse Size Calculator gives Fuse Amps: 20, Required Min Amps: 20.
Ofte Stillede Spørgsmål
Are fuses sized differently than breakers?
Can I round down instead of up to a standard size?
What inputs does the Fuse Size Calculator need?
How accurate is the Fuse Size Calculator?
Is the Fuse Size Calculator free to use?
Om Sikringsstørrelse-beregner
Fuses are overcurrent protective devices that protect electrical circuits and equipment from excessive current that could cause wire overheating, equipment damage, or fire. Selecting the correct fuse size requires balancing two competing requirements: the fuse must be large enough to handle normal operating current without blowing, and small enough to reliably protect the circuit and equipment under fault conditions. The Fuse Size Calculator helps you find the right fuse rating for any application. For general circuit protection, fuses should be rated at or slightly above the maximum expected continuous current. A circuit drawing 12 amps should use a 15-amp fuse, which is the next standard size up. Using a fuse exactly at the operating current risks nuisance blowing due to slight current variations. Standard blade fuse ratings (used in automotive applications): 1, 2, 3, 4, 5, 7.5, 10, 15, 20, 25, 30, 35, 40 amps. Standard glass tube fuse ratings: 0.25, 0.5, 1, 1.5, 2, 3, 4, 5, 7, 8, 10, 12, 15, 20, 25, 30, 35 amps. For motor protection, fuses must accommodate the high inrush current at startup. A dual-element time-delay fuse rated at 125 to 150 percent of the motor's full-load current handles startup surges without blowing while still providing overcurrent protection. For normal motor protection, size the fuse at 125 percent of the full-load current and use a time-delay type. For transformer protection, primary fuse sizing depends on transformer capacity and the reflected secondary load. Primary fuses should not exceed 125 percent of the primary full-load current for transformers over 9 kVA. For electronic equipment protection, use a slow-blow (time-delay) fuse rated 25 to 50 percent above the equipment's rated input current to handle capacitive inrush on power-up without blowing.