CalculatorCast

Calculadora de Tamaño de Fusible

Encuentra el tamaño correcto del fusible usando la regla del 125% para carga continua del NEC.

Introducción

Fuse Size Calculator - Find the correct fuse size using the NEC 125% continuous-load rule. Enter Continuous load (A) to get an instant result.

Fórmula

Same NEC 210.20(A) 125% continuous-load rule used for breakers applies to fuse selection: required rating = continuous load × 1.25, rounded up to the next standard NEC 240.6(A) size.

Paso a paso

  1. Enter the Continuous load (A).
  2. Click Calculate to see your result instantly.

Ejemplo del mundo real

Example: With Continuous load (A) = 16, the Fuse Size Calculator gives Fuse Amps: 20, Required Min Amps: 20.

Preguntas Frecuentes

Are fuses sized differently than breakers?
No - the NEC treats fuses and circuit breakers the same way for overcurrent protection sizing purposes; both use the same 125%-of-continuous-load rule and the same standard ampere ratings in 240.6(A).
Can I round down instead of up to a standard size?
No - the required minimum rating (load × 1.25) must be met or exceeded, so you always round up to the next standard size at or above that value.
What inputs does the Fuse Size Calculator need?
You'll need to provide: Continuous load (A). All fields use sensible defaults, so you can see a working example immediately and then adjust the values to match your own numbers.
How accurate is the Fuse Size Calculator?
The Fuse Size Calculator gives an estimate. Formula used: Same NEC 210.20(A) 125% continuous-load rule used for breakers applies to fuse selection: required rating = continuous load × 1.25, rounded up to the next standard NEC 240.6(A) size. Actual outcomes vary with factors the formula does not capture, so treat the result as a guide, not a guarantee. Entering realistic, correct values gives the most useful result.
Is the Fuse Size Calculator free to use?
Yes, the Fuse Size Calculator is completely free, requires no signup, and runs instantly in your browser.

Acerca de Calculadora de Tamaño de Fusible

Fuses are overcurrent protective devices that protect electrical circuits and equipment from excessive current that could cause wire overheating, equipment damage, or fire. Selecting the correct fuse size requires balancing two competing requirements: the fuse must be large enough to handle normal operating current without blowing, and small enough to reliably protect the circuit and equipment under fault conditions. The Fuse Size Calculator helps you find the right fuse rating for any application. For general circuit protection, fuses should be rated at or slightly above the maximum expected continuous current. A circuit drawing 12 amps should use a 15-amp fuse, which is the next standard size up. Using a fuse exactly at the operating current risks nuisance blowing due to slight current variations. Standard blade fuse ratings (used in automotive applications): 1, 2, 3, 4, 5, 7.5, 10, 15, 20, 25, 30, 35, 40 amps. Standard glass tube fuse ratings: 0.25, 0.5, 1, 1.5, 2, 3, 4, 5, 7, 8, 10, 12, 15, 20, 25, 30, 35 amps. For motor protection, fuses must accommodate the high inrush current at startup. A dual-element time-delay fuse rated at 125 to 150 percent of the motor's full-load current handles startup surges without blowing while still providing overcurrent protection. For normal motor protection, size the fuse at 125 percent of the full-load current and use a time-delay type. For transformer protection, primary fuse sizing depends on transformer capacity and the reflected secondary load. Primary fuses should not exceed 125 percent of the primary full-load current for transformers over 9 kVA. For electronic equipment protection, use a slow-blow (time-delay) fuse rated 25 to 50 percent above the equipment's rated input current to handle capacitive inrush on power-up without blowing.