Calculateur de Charge du Tableau
Estimez la demande totale du tableau électrique et l'intensité (méthode simplifiée NEC 220.42).
Tableau d'amortissement
| # | Paiement | Capital | Intérêts | Solde |
|---|---|---|---|---|
Croissance dans le temps
| Année | Investi | Valeur |
|---|---|---|
Introduction
Panel Load Calculator - Estimate total electrical panel demand load and amperage (simplified NEC 220.42 method). Enter General lighting load (VA), Appliance loads (VA), System voltage (V) to get an instant result.
Formule
A simplified, illustrative demand calculation: general lighting load is counted at 100% for the first 10,000 VA and 40% for the remainder, appliance load is added at 100%, and the total VA is converted to amps via I = VA / V. This is NOT the literal NEC Table 220.42 dwelling-unit demand schedule (which uses 3,000 VA at 100%, 35% from 3,001–120,000 VA, and 25% above that) - real panel/service load calculations must follow NEC Article 220 in full, including the correct occupancy-specific demand factors and all required loads.
Étape par étape
- Enter the General lighting load (VA).
- Enter the Appliance loads (VA).
- Enter the System voltage (V).
- Click Calculate to see your result instantly.
Exemple concret
Example: With General lighting load (VA) = 12000, Appliance loads (VA) = 5000, System voltage (V) = 240, the Panel Load Calculator gives Total Demand Va: 15800, Demand Amps: 65.8333, Basis: Simplified estimate (lighting 100% to 10,000 VA, 40% above; appliances 100%). Not the NEC 220.42 schedule and not for permit or service-size calculations..
Questions Fréquentes
Is this a substitute for a real NEC load calculation?
Why does demand factoring reduce the load at all?
What inputs does the Panel Load Calculator need?
How accurate is the Panel Load Calculator?
Is the Panel Load Calculator free to use?
À propos de Calculateur de Charge du Tableau
Before adding new circuits or major appliances to your home's electrical system, you need to know whether your panel has sufficient remaining capacity. The Panel Load Calculator helps you compute the total electrical load on your service panel, compare it to the panel's rated capacity, and determine whether additional loads can be safely added. Service panel capacity is rated in amps, with the most common residential sizes being 100, 150, and 200 amps. A 200-amp service at 240 volts provides 48,000 volt-amps (48 kVA) of capacity. The NEC permits loading residential services to up to 100 percent of the panel's rating using the optional residential load calculation method, though the first 10,000 volt-amps is counted at 100 percent and the remainder at 40 percent. Load calculation follows NEC Article 220. For a single-family dwelling, the general lighting load is calculated at 3 volt-amps per square foot of living area. Small appliance circuits add 1,500 VA each (minimum two required). The laundry circuit adds 1,500 VA. HVAC loads use the larger of heating or cooling. Fixed appliances over 1,000 watts are included at nameplate rating. The electric range uses a demand factor from NEC Table 220.55. For example, a 2,000 square foot home: lighting at 3 VA/sq ft equals 6,000 VA. Two small appliance circuits add 3,000 VA. Laundry adds 1,500 VA. Total before appliances is 10,500 VA. Under the optional method, 10,000 VA counts at 100 percent and the remainder at 40 percent. A 10,000 VA HVAC unit is added at its full nameplate rating. The total calculated load is then divided by 240 volts to find the required service ampacity. This calculator guides you through the NEC load calculation and shows how much additional capacity remains for new circuits.