מצא את עובי כבל הנחושת THHN המינימלי לזרם נתון לפי טבלת NEC 310.16.

מבוא

Wire Size Calculator - Find the minimum copper THHN wire gauge for a given ampacity per NEC Table 310.16. Enter Desired ampacity (A) to get an instant result.

נוסחה

Looks up the smallest standard copper THHN/THWN-2 conductor whose 75°C ampacity (NEC Table 310.16) meets or exceeds your required current.

צעד אחר צעד

  1. Enter the Desired ampacity (A).
  2. Click Calculate to see your result instantly.

דוגמה מהעולם האמיתי

Example: With Desired ampacity (A) = 30, the Wire Size Calculator gives Awg: 10, Ampacity Amps: 35, Basis: NEC Table 310.16, copper THHN 75°C.

שאלות נפוצות

Should I size for the load or for the breaker?
Wire ampacity must be at least equal to the breaker/fuse rating protecting it (with limited exceptions), and continuous loads should already be increased by 125% per NEC 210.19(A) before you check wire size.
Does this account for temperature or bundling derating?
No - it uses base 75°C copper ampacity from Table 310.16. High ambient temperatures, more than 3 current-carrying conductors bundled together, or aluminum conductors all require further derating per NEC 310.15, which isn't applied here.
Why 75°C and not 60°C or 90°C?
The 75°C column matches most common THHN/THWN-2 conductor terminations and equipment ratings; some devices (especially at 100A or less) are only rated for 60°C terminations, which would require using the lower 60°C ampacity column instead.
What inputs does the Wire Size Calculator need?
You'll need to provide: Desired ampacity (A). All fields use sensible defaults, so you can see a working example immediately and then adjust the values to match your own numbers.
How accurate is the Wire Size Calculator?
The Wire Size Calculator gives an estimate. Formula used: Looks up the smallest standard copper THHN/THWN-2 conductor whose 75°C ampacity (NEC Table 310.16) meets or exceeds your required current. Actual outcomes vary with factors the formula does not capture, so treat the result as a guide, not a guarantee. Entering realistic, correct values gives the most useful result.
Is the Wire Size Calculator free to use?
Yes, the Wire Size Calculator is completely free, requires no signup, and runs instantly in your browser.

אודות מחשבון עובי כבל

Selecting the correct wire gauge is one of the most fundamental decisions in any electrical installation. Undersized wire creates resistance heat that can damage insulation and start fires. Oversized wire wastes money without safety benefit. The Wire Size Calculator helps you determine the appropriate AWG (American Wire Gauge) for any circuit based on current load, run length, and applicable code requirements. Wire sizing involves two considerations: ampacity (the current-carrying capacity of the wire at a safe temperature) and voltage drop (the reduction in voltage over long runs). A wire may be sized adequately for ampacity but still require a larger gauge for voltage drop compliance on long runs. Ampacity is the primary sizing criterion. The NEC specifies the maximum ampacity for each wire gauge based on conductor material (copper or aluminum), insulation type (THHN, THWN, etc.), and installation method. For copper wire with THHN insulation in conduit: 14 AWG is rated 20 amps (15-amp breaker standard), 12 AWG is rated 25 amps (20-amp breaker standard), 10 AWG is rated 35 amps (30-amp breaker standard), 8 AWG is rated 50 amps, and 6 AWG is rated 65 amps. The NEC requires that continuous loads (loads operating for 3 or more hours) do not exceed 80 percent of the circuit's rated ampacity. An air conditioner running continuously on a 20-amp circuit must not draw more than 16 amps continuously. For long runs where voltage drop is a concern, use the voltage drop calculator to determine whether an ampacity-correct wire will also meet the 3 percent voltage drop recommendation. If not, size up one or more gauges until both requirements are met. Aluminum wire is less conductive than copper and requires larger gauges for equivalent ampacity. It is commonly used for large feeder circuits (100 amps and above) where its lower cost provides significant savings despite the larger gauge needed.