Breaker Size Calculator — Find the correct circuit breaker size using the NEC 125% continuous-load rule. Enter Continuous load (A) to get an instant, accurate result.
Formül
NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size.
Adım adım
- Enter the Continuous load (A).
- Click Calculate to see your result instantly.
Gerçek dünya örneği
Example: With Continuous load (A) = 16, the Breaker Size Calculator gives Breaker Amps: 20, Required Min Amps: 20.
Sıkça Sorulan Sorular
Does the 125% rule apply to non-continuous loads too?
Does this list every standard breaker size?
What inputs does the Breaker Size Calculator need?
How accurate is the Breaker Size Calculator?
Is the Breaker Size Calculator free to use?
Devre Kesici Boyutu Hesaplayıcı Hakkında
The Breaker Size Calculator uses a real, verifiable formula — NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size. — so results are accurate every time, not an approximation.