Calculadora de Tamaño de Disyuntor

Encuentra el tamaño correcto del disyuntor usando la regla del 125% para carga continua del NEC.

Introducción

Breaker Size Calculator - Find the correct circuit breaker size using the NEC 125% continuous-load rule. Enter Continuous load (A) to get an instant result.

Fórmula

NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size.

Paso a paso

  1. Enter the Continuous load (A).
  2. Click Calculate to see your result instantly.

Ejemplo del mundo real

Example: With Continuous load (A) = 16, the Breaker Size Calculator gives Breaker Amps: 20, Required Min Amps: 20.

Preguntas Frecuentes

Does the 125% rule apply to non-continuous loads too?
No - the 125% factor specifically applies to continuous loads. For non-continuous loads, the breaker generally only needs to be sized at 100% of the load (subject to wire ampacity and other NEC limits), so mixed continuous/non-continuous loads use a combined calculation.
Does this list every standard breaker size?
It covers the most common residential/light-commercial sizes (15A–100A). NEC 240.6(A) also lists additional standard sizes such as 35A, 45A, 110A, and 125A that aren't included in this simplified lookup.
What inputs does the Breaker Size Calculator need?
You'll need to provide: Continuous load (A). All fields use sensible defaults, so you can see a working example immediately and then adjust the values to match your own numbers.
How accurate is the Breaker Size Calculator?
The Breaker Size Calculator gives an estimate. Formula used: NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size. Actual outcomes vary with factors the formula does not capture, so treat the result as a guide, not a guarantee. Entering realistic, correct values gives the most useful result.
Is the Breaker Size Calculator free to use?
Yes, the Breaker Size Calculator is completely free, requires no signup, and runs instantly in your browser.

Acerca de Calculadora de Tamaño de Disyuntor

Selecting the correct circuit breaker size is essential for electrical safety. An undersized breaker nuisance-trips under normal load. An oversized breaker fails to protect the wire and downstream equipment from overcurrent, potentially allowing unsafe heating before tripping. The Breaker Size Calculator helps you determine the appropriate breaker amperage for any electrical load per NEC requirements. For general loads, the breaker must be rated to handle the maximum continuous load without tripping. The NEC requires that a circuit breaker not be loaded above 80 percent of its rating for continuous loads (loads running for 3 or more hours). This means a 20-amp breaker can supply a maximum continuous load of 16 amps. If your load draws 16 amps continuously, you need a 20-amp breaker. The formula: required breaker size equals (continuous load current divided by 0.80) rounded up to the next standard breaker size. Standard residential breaker sizes are 15, 20, 25, 30, 35, 40, 50, 60, 70, 80, 100, 110, 125, 150, 175, 200 amps. For motor loads, the NEC applies different rules. Branch circuit overcurrent protection for a single-phase motor is typically sized at 250 percent of the motor's full-load current for a thermal-magnetic breaker, or up to 300 percent for an inverse time breaker (per NEC Table 430.52). This larger breaker accommodates the high startup (locked rotor) current that motors draw without nuisance tripping while still protecting against sustained fault currents. For combined loads on a single circuit, sum the individual load currents and apply the 80 percent continuous load rule to the total. If any portion of the load is non-continuous (running less than 3 hours), it counts at 100 percent of its current rather than 80 percent. Always match the breaker rating to the wire gauge: a 20-amp breaker requires 12 AWG wire, a 15-amp breaker requires 14 AWG wire as minimums.