Breaker Size Calculator
Find the correct circuit breaker size using the NEC 125% continuous-load rule.
Amortization schedule
| # | Payment | Principal | Interest | Balance |
|---|---|---|---|---|
Growth over time
| Year | Invested | Value |
|---|---|---|
Introduction
Breaker Size Calculator — Find the correct circuit breaker size using the NEC 125% continuous-load rule. Enter Continuous load (A) to get an instant, accurate result.
Formula
NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size.
Step-by-step
- Enter the Continuous load (A).
- Click Calculate to see your result instantly.
Real-world example
Example: With Continuous load (A) = 16, the Breaker Size Calculator gives Breaker Amps: 20, Required Min Amps: 20.
Frequently Asked Questions
Does the 125% rule apply to non-continuous loads too?
Does this list every standard breaker size?
What inputs does the Breaker Size Calculator need?
How accurate is the Breaker Size Calculator?
Is the Breaker Size Calculator free to use?
About the Breaker Size Calculator
The Breaker Size Calculator uses a real, verifiable formula — NEC 210.20(A)/215.3: for a continuous load (running 3 hours or more), the overcurrent device must be rated at least 125% of the continuous load current, rounded up to the next standard NEC 240.6(A) breaker size. — so results are accurate every time, not an approximation.