Calculadora de Llenado de Caja
Calcula el volumen requerido de la caja eléctrica a partir de conductores, dispositivos y tierras (NEC 314.16).
Tabla de amortización
| # | Pago | Capital | Interés | Saldo |
|---|---|---|---|---|
Crecimiento a lo largo del tiempo
| Año | Invertido | Valor |
|---|---|---|
Introducción
Box Fill Calculator - Calculate required electrical box volume from conductors, devices, and grounds (NEC 314.16). Enter # of 14 AWG conductors, # of 12 AWG conductors, # of 10 AWG conductors, Device yokes (switches/receptacles), to get an instant result.
Fórmula
NEC 314.16(B): required box volume = Σ(conductor count × per-conductor volume allowance by gauge) + (2 × largest-conductor allowance × device yokes) + (largest-conductor allowance, counted once, if any equipment grounding conductors are present).
Paso a paso
- Enter the # of 14 AWG conductors.
- Enter the # of 12 AWG conductors.
- Enter the # of 10 AWG conductors.
- Enter the Device yokes (switches/receptacles).
- Toggle "Ground wires present" on or off as needed.
- Click Calculate to see your result instantly.
Ejemplo del mundo real
Example: With # of 14 AWG conductors = 0, # of 12 AWG conductors = 3, # of 10 AWG conductors = 0, Device yokes (switches/receptacles) = 1, Ground wires present = yes, the Box Fill Calculator gives Required Volume Cu In: 13.5, Basis: NEC Table 314.16(B).
Preguntas Frecuentes
Why do device yokes (switches/receptacles) count double?
Why are all grounding conductors counted as just one allowance?
Does this cover every box-fill exception?
What inputs does the Box Fill Calculator need?
How accurate is the Box Fill Calculator?
Is the Box Fill Calculator free to use?
Acerca de Calculadora de Llenado de Caja
Electrical junction boxes and device boxes must be large enough to contain all conductors, devices, and fittings without overcrowding, which could damage wire insulation and create safety hazards. The Box Fill Calculator determines the minimum required box volume per NEC Article 314, ensuring code compliance for any wiring configuration. The NEC uses a volume allowance method to calculate box fill. Each conductor, device, fitting, and clamp counts as a certain number of conductor equivalents based on the largest conductor in the box. The required box volume is the total conductor equivalents multiplied by the volume allowance per conductor for that gauge. Volume allowances per conductor by gauge: 18 AWG requires 1.5 cubic inches per conductor equivalent. 16 AWG requires 1.75 cubic inches. 14 AWG requires 2.0 cubic inches. 12 AWG requires 2.25 cubic inches. 10 AWG requires 2.5 cubic inches. 8 AWG requires 3.0 cubic inches. 6 AWG requires 5.0 cubic inches. Conductor counting rules: each current-carrying conductor (hot or neutral) entering the box from outside counts as 1. All equipment grounding conductors together count as 1 if they are all the same gauge or smaller than the largest current-carrying conductor. Internal cable clamps together count as 1 (regardless of number). Each switch or receptacle device counts as 2. For a typical bedroom outlet box with one 14/2 NM cable (1 hot, 1 neutral entering) plus the equipment ground, 2 conductors plus 1 EGC (as 1) plus clamps (1) plus device (2) equals 7 conductor equivalents. At 2.0 cubic inches per equivalent, the required volume is 14 cubic inches. A standard 2x4 single-gang box has 18 to 22 cubic inches, which is adequate.