ボックス充填計算機
導体、器具、接地線から必要な電気ボックスの容積を計算します(NEC 314.16)。
返済スケジュール
| # | 支払い | 元金 | 利息 | 残高 |
|---|---|---|---|---|
時間経過による成長
| 年 | 投資額 | 値 |
|---|---|---|
はじめに
Box Fill Calculator - Calculate required electrical box volume from conductors, devices, and grounds (NEC 314.16). Enter # of 14 AWG conductors, # of 12 AWG conductors, # of 10 AWG conductors, Device yokes (switches/receptacles), to get an instant result.
計算式
NEC 314.16(B): required box volume = Σ(conductor count × per-conductor volume allowance by gauge) + (2 × largest-conductor allowance × device yokes) + (largest-conductor allowance, counted once, if any equipment grounding conductors are present).
ステップごとの説明
- Enter the # of 14 AWG conductors.
- Enter the # of 12 AWG conductors.
- Enter the # of 10 AWG conductors.
- Enter the Device yokes (switches/receptacles).
- Toggle "Ground wires present" on or off as needed.
- Click Calculate to see your result instantly.
実例
Example: With # of 14 AWG conductors = 0, # of 12 AWG conductors = 3, # of 10 AWG conductors = 0, Device yokes (switches/receptacles) = 1, Ground wires present = yes, the Box Fill Calculator gives Required Volume Cu In: 13.5, Basis: NEC Table 314.16(B).
よくある質問
Why do device yokes (switches/receptacles) count double?
Why are all grounding conductors counted as just one allowance?
Does this cover every box-fill exception?
What inputs does the Box Fill Calculator need?
How accurate is the Box Fill Calculator?
Is the Box Fill Calculator free to use?
ボックス充填計算機について
Electrical junction boxes and device boxes must be large enough to contain all conductors, devices, and fittings without overcrowding, which could damage wire insulation and create safety hazards. The Box Fill Calculator determines the minimum required box volume per NEC Article 314, ensuring code compliance for any wiring configuration. The NEC uses a volume allowance method to calculate box fill. Each conductor, device, fitting, and clamp counts as a certain number of conductor equivalents based on the largest conductor in the box. The required box volume is the total conductor equivalents multiplied by the volume allowance per conductor for that gauge. Volume allowances per conductor by gauge: 18 AWG requires 1.5 cubic inches per conductor equivalent. 16 AWG requires 1.75 cubic inches. 14 AWG requires 2.0 cubic inches. 12 AWG requires 2.25 cubic inches. 10 AWG requires 2.5 cubic inches. 8 AWG requires 3.0 cubic inches. 6 AWG requires 5.0 cubic inches. Conductor counting rules: each current-carrying conductor (hot or neutral) entering the box from outside counts as 1. All equipment grounding conductors together count as 1 if they are all the same gauge or smaller than the largest current-carrying conductor. Internal cable clamps together count as 1 (regardless of number). Each switch or receptacle device counts as 2. For a typical bedroom outlet box with one 14/2 NM cable (1 hot, 1 neutral entering) plus the equipment ground, 2 conductors plus 1 EGC (as 1) plus clamps (1) plus device (2) equals 7 conductor equivalents. At 2.0 cubic inches per equivalent, the required volume is 14 cubic inches. A standard 2x4 single-gang box has 18 to 22 cubic inches, which is adequate.